Requirements For Straight Pipe Sections When Installing Vortex Flowmeters
Dec 06, 2018

The requirements for straight pipe sections during vortex flowmeter installation are very important. Its detailed requirements are as follows:

The flowmeter has certain requirements on the upstream and downstream straight pipe sections at the installation point, otherwise it will affect the measurement accuracy.

If there is a tapered tube upstream of the installation point of the flowmeter, there should be a straight pipe section of not less than 15D (D is the pipe diameter) upstream of the flowmeter, and a straight pipe section of not less than 5D in the downstream.

If there is a diverging pipe upstream of the installation point of the flowmeter, the upstream of the flowmeter shall have a straight pipe section of not less than 18D (D is the pipe diameter), and the downstream shall have a straight pipe section of not less than 5D.

If there is a 90° elbow or a downward joint upstream of the installation point of the flowmeter, there should be a straight pipe section of not less than 20D upstream of the flowmeter, and a straight pipe section of not less than 5D downstream.

 If there is a 90° elbow on the same plane upstream of the installation point of the flowmeter, there should be a straight pipe section of not less than 25D upstream of the flowmeter, and a straight pipe section of not less than 5D downstream.

The flow regulating valve or pressure regulating valve should be installed as far as possible downstream of the flowmeter 5D. If it must be installed upstream of the flowmeter, the upstream of the flowmeter should have a straight pipe section of not less than 25D, and the downstream should have a straight pipe section of not less than 5D. .

If there is a piston type or plunger type pump in the upstream of the flowmeter, a piston type or a Roots type fan and a compressor, there should be a straight pipe section of not less than 25D upstream of the flowmeter, and a straight pipe section of not less than 5D in the downstream.


  • Newsletter
  • Categories
  • Contact Us
    Beijing Gallop Technology Co.,Ltd
    Add:Room410 Tower C, Jiahua Buiding NO.9 Shangdi 3 Street Haidian District, Beijing
    Tel:+86-010-51269778
    Fax:+86-010-62967939
    Mobile:+86-13858586115
    E-mail:13858586115@163.com
  • QR Code
  • Copyright © Beijing Gallop Technology Co.,Ltd All Rights Reserved.